The HVA60 AC hipot is a portable 0.1 Hz VLF cable test system for the testing of medium voltage cables. At only 57 kg this compact AC hipot is truly quite remarkable and as such is ideal for mobile use.
The powerful output is capable of driving capacitive loads of up to 10 μF. At maximum output voltage cables with a length of up to 15 km can be tested. The HVA60 AC hipot offers various operating modes. Cable testing, cable sheath / jacket testing, sheath fault location, cable fault conditioning (burning), vacuum bottle test.
Predefined standard-compliant cable test sequences
Symmetrical sine wave at high voltage
RMS measurement of output voltage and current
Measurement of capacitive and resistive load
Automatic load dependent frequency selection (0.01 Hz – 0.1 Hz)
Display of current test time
Integrated real-time scope function
Self-explanatory, multilingual software
Automatic measurement reporting
Report storage via USB or RS232
PC software (b2 ControlCenter) for data analysis and storage
Flashover detection and ultra fast switch off
Flashover voltage measurement
Time optimized burning mode